Haddad, Abderrahmane, Naylor, P., Metwally, I. A., German, D.M. and Waters, Ronald 1995. An Improved Non-Inductive Impulse Voltage Measurement Technique for ZnO Surge Arresters. IEEE Transactions on Power Delivery 10 (2) , pp. 778-785. 10.1109/61.400853 |
Official URL: http://dx.doi.org/10.1109/61.400853
Abstract
One of the most important parameters of the protective performance of ZnO surge arresters is the residual voltage. In laboratory tests on standard arresters, a thin ZnO disc with a central hole is used in order to pick up the voltage, and a system with a double shielding technique reduces outside effects. Comparative tests of voltage signals from this series divider with those from a conventional parallel connected divider show that inductive overshoot is avoided